14 bits input, 2 channel voltage 0/10-0/15
2 channel t temperature testing.
2 channel input, 2 channel output. 2 groups of pid parameter.
14/10 bits high precision analog output.
2 channel voltage 0/10v or0/5v
8 channels analog input (14bit): 4 channels current input, 4 channels
voltage input.
4 channels analog input (14bit);
2 channels analog output (12bit): current / voltage selectable.
4 channels analog output (12bit): current / voltage selectable.
-150 t (53 pages)
XP3-BD User Manual Index Page Chapter 1 Configuration of the BD-Board 1-1 Configuration Chapter 2 AI and temperature sampling board XP3-2AD2PT-BD 2-1 General 2-2 Specs 2-3 External installations and connections 3-4 Assignment of input ID 2-5 Working Mode settings 2-6 Control settings 2-7 Application of PID output value 2-8 Programs Chapter 3 K type thermo coupling temperature PID board XP3-2TC-P-3D...
Configuration of the BD-Board 1-1.Configuration 1-1 Configuration 1. Install BD correctly on the main unit; 2. Then connect the model online via XCP edit tool, in the “Window” menu, choose “Config BD Board(C)” (Image 1). 3. Click it, in the “Config BD Board(C)” dialog box, choose “Other BD” (Just as shown in graph and click “OK”...
Page 4
AI and temperature sampling board XP3- 2AD2PT-BD 2-1.General 2-2.Specs 2-3.External installations and connections 2-4.Assignment of input ID 2-5.Working Mode settings 2-6.Control settings 2-7.Application of PID output value XP3-BD User Manual Page 4 of 30 MANUL008R2V1...
2-2 Specs Item Voltage Input Temperature Input Analogue Input DC: 0 to 5V, 0 to 10V Platinum Resistor PT100 (Input resistor 300kΩ) Signal (2-wire format) Temperature -100 to 350 degrees C Testing band Resolution 0.15mV 10/16383 Digital Output 0 to 16383 -1000 to 3500 band Integrate...
2-3 External installations and connections 1) The Installation of Board: Open the board’s cover at the back of XP3 (As shown in the following image); install it according to the pin arrangement. Then fix it with screws, close the cover. Board’s install position 2) Connection: See the following diagram...
2-4 Assignment of input ID This BD board does not use standard I/O units memory addresses, the converted data will be directly sent into PLC register. The channels correspond to the PLC register ID: Channel AD signal/Temperature ID1000 ID1001 ID1002 ID1003 value PID output value...
2-5 Working Mode settings 1) Expansion’s input has voltage 0/5V and 0/10V. These FD8306 H O O O O two modes and filter form to select. Set via special FLASH data register FD8306 in PLC. Refer to the graph (right) each register set the 4 channels’...
2-6 Control settings 1. Usage of four parameters: Proportion parameter (Kp), integral parameter (Ki), differential parameter (Kd), control proportion band (Diff) Parameter P is the proportion parameter. Parameter I is the integral parameter. Parameter D is differential parameter ...
2-8 Programs E.g.1: Real time readings of the AD value of CH0, and then carries on PID parameters setting with CH0, then read the PID output value. M8000 Set CH0’s value as 800 K800 QD1000 QD1004 Set CH0’s Kp as 30 QD1005 Set CH0’s Ki as 5 K500...
Page 12
E.g.2. PID temperature control example M8000 K800 QD1002 Set CH2’s value as 800 (80 degrees) QD1009 Set CH2’s Kp as 30 QD1010 Set CH2’s Ki as 5 K500 QD1011 Set CH2’s Kd as 500 Set CH2’s Diff as 150 K150 QD1012 M8000 Convert PID output value (0/4095) to be...
K Type thermo coupling temperature PID board XP3-2TC-P-3D 3-1. General 3-2.Specs 3-3.External installations and connections 3-4.Assign input/output ID 3-5.Working Mode settings 3-6.Control speciality 3-7.Programs 3-1 General Analogue input used by thermocouple (K type) temperature sensor 2 channels input, 2 channels output ...
Page 14
3-2 Specs Item Content Analogue Input Signal Thermocouple K type Input Points 2 points Temperature Testing Band 0 to 970°C Digital Output Band 0~9700, 16 bits binary Output Points 2 points Output Format NPN collector open circuit transistor output Control Precision 0.4°C Resolution 0.1°C...
3-3 External installations and connections Installation Method of Expand Board: 1. Open the expansion cover behind XP3 (See the following diagram), then install according to the pin and fix with screws. Install Position of Expansion Board 2. Connection Method XP3-BD User Manual Page 15 of 30 MANUL008R2V1...
Page 16
Output terminals: Transistor output terminals - please choose DC5V to 30V-regulated power. Circuit insulation: Between programmable controller’s interior circuit and output transistor, use optical coupling device to insulate. Each public module is divided separately Response time: The time from PLC drive optical coupling device to transistor ON/OFF is not more than 0.2ms. ...
Page 17
3-4 Assign input/output ID This BD expansion does not use I/O unit, the converted data is directly sent into PLC register, also add two extra output points. Extra outputs do not include normal system’s I/O output. Channels correspond to the PLC register ID: Channel Current Diff...
3-5 Working Mode settings Set the expansion’s working mode via special FLASH FD8306 H O O O O data register FD8306 in PLC. Refer to the graph by the right, each register has 16 bits, from low bit to high bit, every 4 bits confirm 1 channel’s mode.
Page 19
3-6 Control specialities 1. Usage of Four Parameters: Proportion parameter (Kp), integral parameter (Ki), differential parameter (Kd), control proportion band (Diff) Parameter P is the proportion parameter: Parameter I is the integral parameter, mainly used to remove net difference. Parameter D is the differential parameter, mainly used to control signal’s change trend. Temperature Control Band Means: in the assigned band, to carry out PID control,beyond the band does not carry out PID control.
3-7 Programs Program with CH0 M8000 K800 QD1000 Set value in CH0 as 800 (80 degrees) Set CH0’s Kp as 30 QD1001 QD1002 Set CH0’s Ki as 5 Set CH0’s Kd as 500 K500 QD1003 Set CH0’s Diff as 150 K150 QD1004 (i.e., carry on PID operation at...
Analogue AI/AO temperature sampling board XP3-2PT2ADIDA-BD 4-1. General 4-2.Specs 4-3.External installations and connections 4-4.Assignment of input ID 4-5.Working Mode settings 4-6.Control settings 4-7.Programs XP3-BD User Manual Page 21 of 30 MANUL008R2V1...
Page 22
4-1 General 14 bits high precision analog input 10 bits high precision analog output 2 channels voltage 0/10V or 0/5V (selectable) analog input 2 channels PT temperature testing resistor (PT100 2-wire format) temperature sensor analog input XP3-BD User Manual Page 22 of 30 MANUL008R2V1...
Page 23
4-2 Specs Item Voltage Input Temperature Input D/A output DC: 0to 5V, 0 to 10V Analogue Platinum resistor PT100 (Input Resistance Input Signal (2-wire format) 300kΩ) Digital Input 10 bits Binary band (0/1023) Analogue 0/20mA, 4/20mA Output band Temperature Testing -100 to 350°C band Distinguish...
Page 24
4-3 Extension installations and connections 1. Installation method of the expansion board: Open the board’s cover at the back of XP3 (As shown in the following graph), and then install it according to the pin arrangement. Then fix it with screws, close the cover. Board’s install position 2.
Page 25
4-4 Assignment of input ID This BD board does not use I/O units, the converted data will be sent directly into the PLC register. The channel’s corresponding PLC register ID is: Channel AD signal/Temperature ID1000 ID1001 ID1002 ID1003 value PID output value ID1004 ID1005 ID1006...
4-5 Working mode settings 1) Expansion’s input cards have voltage 0/5V, FD8306 H O O O O 0/10V these two modes and filter form to select. Set via special FLASH data register FD8306 in PLC. Refer to the graph by the right;...
Page 28
4-6 Control specialities 1. Usage of Four Parameters: Proportion parameter (Kp), integral parameter (Ki), differential parameter (Kd), control proportion band (Diff). Parameter P is the proportion parameter. Parameter I is the integral parameter, mainly used to remove net difference. Parameter D is the differential parameter, mainly used to control signal’s change trend. Temperature Control Band Means: in the assigned band, to carry out PID control, beyond the band does not carry out PID control.
4-7 Programs The following example is a sample Program & corresponding description: M8000 ID1000 Write channel 0 (input temperature) into D0 ID1001 Write channel 1 (output temperature) into D2 Treat CH2 (Pressure setting 0/10V) as the ID1002 QD1004 set value in CH3 ID1003 Write CH3 (Pressure Feedback) into D4 QD1009...
Page 30
Documentation Reference Document Number Revision Date MANU L008 05/07/2011 XINJE IS A REGISTERED TRADEMARK OF XINJE ELECTRICAL CO.LTD. REPLICATION OF THE INFORMATION CONTAINED WITHIN THIS DOCUMENT WITHOUT PRIOR NOTIFICATION AND AGREEMENT IS PROHIBITED. Engineered and supplied by: International partners with: Web: www.listo-ltd.com...