Example 2:
Application of PID control in AD modules
The following, we take channel 0 of XC-E8AD as the example:
M8000
MOV
MOV
MOV
MOV
MOV
MOV
MOV
MOV
M8000
XC series analog expansions User Manual Page 18 of 53
ID100
D10
D4000
QD100
K30
QD108
K10
QD109
K300
QD110
K100
QD111
K200
QD112
ID108
D1000
Y100
END
Write channel 0's data into data register D10
Channel 0's set value is register D4000
Set proportion coefficient Kp as 30
Set proportion coefficient Ki as 10
Set proportion coefficient Kd as 300
Set adjustment band Diff as 100
Set control dead area as 200
Write channel 0's PID value into register D1000
PID start/stop signal
MANU003R2V1