Register FD8251 low byte:
Channel 5
Bit7
Bit6
00: 1/2 filter
01: no filter
10: 1/3 filter
11: 1/4 filter
E.g. 1 If set working mode 0-20mA / 4-20mA, 0-10V / 0-5V filters are all 1/2 filter, value in
FD8250 is 2301H
4-4 External connections
When connecting 24V power, use 24V power on PLC main unit to avoid interference.
To avoid interference, use shielded cable and single point grounding with the shield.
Module's 0-20mA or 4-20mA output need 24V external power, the module adjusts the loop
circuit's current, but the module itself doesn't produce current.
XC series analog expansions User Manual Page 27 of 53
Bit5
Bit4
0: voltage
0:0~10V
input
1:0~5V
1: current
0:0~20mA
input
1:4~20mA
Channel 4
Bit3
Bit2
00: 1/2 filter
01: no filter
10: 1/3 filter
11: 1/4 filter
Bit1
Bit0
0:
0:0~10V
voltage
1:0~
input
5V
0:0~20m
1:
A
current
1:4~
input
20m
A