5-1 Specifications
Items
Analog output range
Digital output range
Resolution Ratio
Resolution
Conversion speed
Isolation format
Power usage
Installation format
External size
XC series analog expansions User Manual Page 31 of 53
Voltage output
DC0-5V / 0-10V
12 bits binary data
1/4096(12Bit); the converted data is stored into PLC with the format
of HEX
0.8%
2ms per channel
DC/DC convert, optical coupling isolation
DC24V±10%,100mA
Can be fixed with M3 screws or directly installed on DIN rail
63mm × 102mm × 73.3mm
Characteristic
12 bits high precision
analog output
4 channels selectable
voltage 0-5V / 0-10V,
current 0-20mA / 4-
20mA output
Up to 7 modules can
be fitted
Current output
DC0-20mA / 4-20mA
MANU003R2V1