Troubleshooting By Indication On The Remote Controller; External Protection Device Abnormality - Daikin SkyAir RZQ-P Series Service Manual

Cooling only / heat pump
Hide thumbs Also See for SkyAir RZQ-P Series:
Table of Contents

Advertisement

SiUS28-902_B
3. Troubleshooting by Indication on the Remote
Controller
3.1

External Protection Device Abnormality

A0
Remote
Controller
Display
Applicable
All indoor models
Models
Method of Error
Detect open or short circuit between external input terminals in indoor unit.
Detection
Error Decision
When an open circuit occurs between external input terminals with the remote controller set to
"external ON/OFF terminal".
Conditions
 Actuation of external protection device
Supposed
 Improper field setting
Causes
 Defective indoor unit PCB
Troubleshooting
Service Diagnosis
Be sure to turn off the power switch before connecting or disconnecting
Caution
the connector or parts may be damaged.
External
protection device is
connected to terminals T1
and T2 of the indoor
unit terminal
NO
Check the setting state of the
external ON/OFF input by
remote controller.
ON/OFF
input from
outside (mode No. 12,
first code No. 1) has been
set to external protection
device input (second
code No. 03)
by remote
controller.
NO

Troubleshooting by Indication on the Remote Controller

YES
YES
Actuation of external protection
device.
Change the second code No. to
"01" or "02" .
Replace the indoor unit PCB.
89

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents