SiUS28-902_B
3. Troubleshooting by Indication on the Remote
Controller
3.1
External Protection Device Abnormality
A0
Remote
Controller
Display
Applicable
All indoor models
Models
Method of Error
Detect open or short circuit between external input terminals in indoor unit.
Detection
Error Decision
When an open circuit occurs between external input terminals with the remote controller set to
"external ON/OFF terminal".
Conditions
Actuation of external protection device
Supposed
Improper field setting
Causes
Defective indoor unit PCB
Troubleshooting
Service Diagnosis
Be sure to turn off the power switch before connecting or disconnecting
Caution
the connector or parts may be damaged.
External
protection device is
connected to terminals T1
and T2 of the indoor
unit terminal
NO
Check the setting state of the
external ON/OFF input by
remote controller.
ON/OFF
input from
outside (mode No. 12,
first code No. 1) has been
set to external protection
device input (second
code No. 03)
by remote
controller.
NO
Troubleshooting by Indication on the Remote Controller
YES
YES
Actuation of external protection
device.
Change the second code No. to
"01" or "02" .
Replace the indoor unit PCB.
89