Troubleshooting by Indication on the Remote Controller
3.38 Power Supply Voltage Abnormality
U2
Remote
Controller
Display
Applicable
RZR, RZQ
Models
Method of Error
The error is detected according to the voltage of main circuit capacitor built in the inverter and
Detection
power supply voltage.
Error Decision
When the abnormal voltage of main circuit capacitor built in the inverter and abnormal power
Conditions
supply voltage are detected
Power supply insufficient
Supposed
Instantaneous power failure
Causes
Defective outdoor unit fan motor
Defective outdoor control PCB (A1P)
Defective main circuit wiring
136
SiUS28-902_B
Service Diagnosis