Daikin SkyAir RZQ-P Series Service Manual page 63

Cooling only / heat pump
Hide thumbs Also See for SkyAir RZQ-P Series:
Table of Contents

Advertisement

SiUS28-902_B
Auto Restart after Power Failure Reset
For the air conditioners with no setting for the function, the units will be left in the stop condition
when the power supply is reset automatically after power failure reset or the main power supply
is turned on again after once turned off. However, for the air conditioners with the setting (same
as factory setting), the units may start automatically after power failure reset or the main power
supply turned on again (return to the same operation condition as that of before power failure).
For the above reasons, when the unit is set enabling to utilize "Auto restart function after power
failure reset", utmost care should be taken in the following circumstances:
Caution 1. The air conditioner starts operation suddenly after power failure reset or
2. During servicing, if the main power switch is turned off, and then back on
Setting of Airflow Direction Adjustment Range
Make the following airflow direction setting according to the respective purpose.
Test Operation
the main power supply turned on again..
again after completion, the unit will startup and the fan will rotate.
Mode No.
First Code No.
13 (23)
Second Code No.
01
02
4
03
Field Setting
Setting
Upward (Draft prevention)
Standard
Downward (Ceiling soiling
prevention)
55