Troubleshooting by Indication on the Remote Controller
3.15 High Pressure Abnormality
E3
Remote
Controller
Display
Applicable
RZR, RZQ
Models
Method of Error
Abnormality is detected when the contact of the high pressure protection switch opens.
Detection
Error Decision
Error is generated when the S1PH (High pressure switch) activation count reaches the number
Conditions
specific to the operation mode.
(Reference) Operating pressure of high pressure switch
Operating pressure: 580 psi
Reset pressure:
Actuation of outdoor unit high pressure switch
Supposed
Defective high pressure switch
Causes
Defective outdoor unit PCB
Instantaneous power failure
Defective high pressure sensor
106
435 psi
SiUS28-902_B
Service Diagnosis