At startup with thermostat ON or after the completion of defrosting in heating operation, the
indoor unit fan is controlled to prevent cold air from blasting out and ensure startup capacity.
[Detail of operation]
When either the starting condition 1 or the starting condition 2 is established, the operations
shown below will be conducted.
Function
Hot start starting conditions
• Starting condition 1: Defrost ending or
OR
oil return ending
• Starting condition 2: Thermostat ON
Hot start control
H/L remote
controller setting
LL
OFF
ON
OFF
ON
OFF
Hot start in progress
The fan is not OFF before initiating the hot start: LL
The fan is OFF before initiating the hot start: OFF
The fan is ON: ON
The fan is OFF: OFF
TH
: Temperature detected with the gas thermistor
2
TC: High pressure equivalent saturated temperature
Outline of Control (Indoor Unit)
Hot start ending conditions
• lapse of 3 minutes
OR
• TH2 > 93˚F
• Tc > 126˚F
Hot start delay
30 sec.
Normal control
Normal control
Normal control