2.7.
Timers
A unit may have up to 5 selectable timers for each system on a controller. All timers are associated with their
system, so for a % of post bleed timer looks at the bleed of that system.
2.7.a. Timer Type Selection
A pop-up screen lets you scroll through the various timer types available.
2.7.b. Timer Set Up
27.c. Pulse Timer
TIMERS - Select the type (28-day, pulse, limit, percent
or percent of post blowdown) as well as the run times
of each timer available per system.
Pulse - A water meter activated timer
Limit - Feed with bleed with a maximum run time or
limit for one bleed cycle.
Recycle - A continuous recycle timer with ON and OFF
settings.
Percent Post Bleed - For feed after bleed for a settable
percentage of the bleed time with a maximum run time.
28-Day - A biocide or event timer.
Each timer type selected will have its own unique Set
the type of timer selected. The page displayed before
entering the Set Up menu of a timer provides an overall
review of the timers current settings.
ACCUMULATE - The number of gallons or liters from
water meter to count before activating timer.
RUN TIME - The amount of time for the timer to run
METER INPUT - Select water meter 1 or 2 for the
only if the meters have the same contact value.
BLEED INTR - Allows the pulse timer to be interrupted
during conductivity bleed. While interrupted, you can also
store for playback.