Mitsubishi Electric MELSEC iQ-R Series User Manual page 35

Controller module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

(5)
(2)
(4)
(5)
■Mode selection
Mode
Dot matrix LED display
10
0010
11
0011
Do not reset the C Controller module during initialization.
Perform the initialization again if the module has been reset in error.
Abnormal completion of initialization process
Upon abnormal completion of the initialization, the ERROR LED will be flashing, and the READY LED and USER LED turn
ON. In the case of abnormal completion, perform the initialization again.
■The ERROR LED flashes, and the value other than '0000' is displayed on the dot matrix LED
The ERROR LED flashes, and the value corresponding to the error is displayed.
Dot matrix LED
Error name
E100
Initialization function
execution error
E101
Firmware update function
execution error
E102
For an abnormal completion, check the error corresponding to the value displayed on the dot matrix LED, and take the
appropriate corrective action. If the error occurs again, please consult your local Mitsubishi representative.
Module status after initialization
After initialization, the status of the C Controller module will be as follows:
■Default IP setting
• The registered script file stops to be executed.
• The IP address for the C Controller module is set to the default. (Page 23 Ethernet Ports)
*1 The script file name is renamed as "STARTUP.BAK", and deregistered.
■Module initialization setting
• Default parameters are set to the data memory.
• The program memory, device/label memory, and data memory are formatted.
• A security password is initialized. (Default password: password)
7.
The initialization is performed by resetting the module. The
READY LED (5) will turn ON, and the BUS RUN LED (2) and
USER LED (4) will be flashing during the initialization.
8.
Upon normal completion of the initialization, the BUS RUN
LED (2) and USER LED (4) turns OFF, and the READY LED
(5) starts flashing.
9.
Reset the C Controller module.
(Page 41 RESET/STOP/RUN switch)
Description
Default IP setting
Module initialization setting
Cause
The execution of the initialization function failed.
For details on the firmware update function, refer to the following manual.
MELSEC iQ-R Module Configuration Manual
*1
Corrective action
Execute the initialization again.
6 PROCEDURE BEFORE OPERATION
6.1 Initialization
6
33

Advertisement

Table of Contents
loading

This manual is also suitable for:

R12ccpu-v

Table of Contents