Considerations - Mitsubishi Electric MELSEC iQ-R Series User Manual

Controller module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Considerations

The modules requiring particular attentions are shown below.
For details, refer to the manual for the module used.
I/O module
■High-speed input module
• When the module is used as a high-speed input module, select the following model in accordance with the ON/OFF of a
noise filter. The module operates with the default setting when the ON/OFF of the noise filter does not correspond to the
ON/OFF of the model.
Module name
QX40H
QX70H
QX80H
QX90H
• When the module is used as an interrupt module, select "QI60". The module operates with the default setting when it is
used with the noise filter set to OFF.
• When using one or more modules as interrupt modules, set the number of modules to be used in "I/O Assignment Setting"
of the "System Parameter" screen.
■Interrupt module
When using one or more modules, set the number of modules to be used in "I/O Assignment Setting" of the "System
Parameter" screen.
High-speed counter module and pulse input module
Check the latest error code with the System Monitor function since error codes for QD63P6 and QD60P8-G cannot be
checked with the Module Diagnostic function. When more than one error occurred, refer to the buffer memory.
Positioning module
• Set parameters in a user program because the positioning data parameter cannot be written to the module.
• Check the latest error code with the System Monitor function since error codes for QD70P4, QD70P8, QD70D4, and
QD70D8 cannot be checked with the Module Diagnostic function. When more than one error occurred, refer to the buffer
memory (error codes for each axis).
Loop control module
Check the latest error code with the System Monitor function since error codes for the Q62HLC cannot be checked with the
Module Diagnostic function. When more than one error occurred, refer to the buffer memory.
APPX
106
Appendix 2 How to Use MELSEC-Q Series Modules
Model name displayed on CW Configurator
Noise filter: ON
QX40H (NoiseF_ON)
QX70H (NoiseF_ON)
QX80H (NoiseF_ON)
QX90H (NoiseF_ON)
Noise filter: OFF
QX40H (NoiseF_OFF)
QX70H (NoiseF_OFF)
QX80H (NoiseF_OFF)
QX90H (NoiseF_OFF)

Advertisement

Table of Contents
loading

This manual is also suitable for:

R12ccpu-v

Table of Contents