Service Reminder" Function - Riello Condexa PRO NA 75P Installation, Operation And Service Manual

Hide thumbs Also See for Condexa PRO NA 75P:
Table of Contents

Advertisement

COMMISSIONING AND MAINTENANCE
9
WARNING: Before carrying out any maintenance or cleaning,
disconnect the power from the device by turning off the main
switch and closing the main gas valve. In addition, for all
maintenance (to be carried out at least once a year, as noted
above) always replace all the boiler's internal flue and gas
seals, in particular the burner seals, when servicing these
components.
Before performing any operation:
− disconnect the electric power supply by turning the main
system switch to "off"
− close the gas shut-off valve.
GAS LEAKING INSPECTION
Verify all gas piping to ensure that there are no leaks.
9
DANGER: To verify the gas leaks use a soap solution or a gas
leak detector. Do not use matches, candles, or other methods
that can cause explosions!
CHECK EXHAUST AND COMBUSTION AIR PIPE SYSTEM
Clear vent systems of any obstructions, corrosion, physical dam-
age, water stains, rust. Verify the connection between the single
components.
Verify the outside terminations are clear. Clean the screens and the
louvers if there is any debris.
INSPECTION OF IGNITION ELECTRODE
Verify that the electrode is clean of deposits and use an emery
cloth or other material to remove deposits as required.
1
1
Ignition/detection electrode
2
Flame sensor
CHECKING FOR WIRING AND CONNECTIONS
Check that all wiring is securely fastened and in good condition
without any cracking or alteration of isolation or presence of cor-
rosion in metallic connection.
1
2
0.12"-0.16"
(3-4mm)
BURNER GASKET INSPECTION
You must maintain the boiler as outlined in this manual and have
the boiler started up and serviced at least annually by a qualified
service technician to ensure boiler/system reliability.
This includes a combustion test and the cleaning of the combus-
tion chamber.
When disassembling the heat exchanger it is crucial to inspect the
Burner Gasket for damage.
It is a must to replace the burner gasket when servicing and if
there are any signs of wear, deformity or discoloration of the gas-
ket and in any case not later than every two years.

4.14.1 "Service reminder" function

The boiler is equipped with a function that reminds the user of the
need to carry out planned maintenance on the appliance after a
number of hours defined in the maintenance plan.
When this maintenance activity is required, the following text ap-
pears on the normal display: "Maintenance required!"
This text will remain active until a qualified service agency resets
the internal meter after maintaining the appliance.
The user can check at any time how many hours until the next
planned maintenance activity by accessing the "Information"
menu
Menu
"
"
Central Heating (CH)
"
Domestic Hot Water (DHW)
"
Information
"
"
Settings
"
"
and selecting "Maintenance" using the ▲ / ▼ buttons
Information
"
"
Service
"
"
The menu also shows the hours from the last maintenance activ-
ity performed and access to a log that lists the dates of the last 15
maintenance activities, if this function has been utilized.
Service
"
"
Service history
"
"
Burn hours since last service
"
Burn hours till service
"
Reset Service Reminder
"
88
"
"
"
"
"

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Condexa pro na 117pCondexa pro series2014259420142595

Table of Contents