COMMISSIONING AND MAINTENANCE

4.10 Converting gas type

4.10.1 Converting gas type LPG

The Condexa PRO NA is equipped for natural gas. It can be convert-
ed to LPG (propane) using the appropriate accessory kit 20150039
(75 P) - 20150040 (117 P).
9
WARNING: Conversion can only be executed by qualified in-
staller, service agency or gas supplier.
9
WARNING: For the conversion, follow what is written in this
manual, according with the safety rules and instructions pro-
vided in the kits supplied
9
WARNING: If the information contained in these instructions is
not properly performed or performed by personnel not prop-
erly trained, there is a potential risk of fuel leakage and/or
carbon monoxide production resulting in substantial property
damage, severe personal injury or death.
9
WARNING: Conversion is not complete until all the control
steps described in these instructions have been carried out.
9
WARNING: After conversion, calibrate the CO2 as shown in the
"Combustion Analysis" section.
Before making the conversion:
− make sure that the master switch and the boiler switch are
in the "Off" position
− check that the gas shutoff valve is closed.
To install the gas conversion kit:
− remove the locking screw
− pull the front panel outwards and then to the top to re-
move it from points A.
A
A
− unscrew the nuts (1) that connect the fan to the upper
flange of the heat exchanger
− remove the flexible air intake pipe (2), by unscrewing the
metal collars (3)
− remove the tube (4), that connects the mixer and the gas
valve