4.11 Combustion Analysis

The Condexa PRO NA is supplied for operation with natural gas, as
indicated by the rating plate, and has already been factory-cali-
brated by the manufacturer.
However, if it is necessary to repeat the adjustments, for example
after non-scheduled maintenance, replacing the gas valve or af-
ter gas conversion from natural gas to LPG, or vice versa, proceed
as described below.
9
WARNING: Adjustments to maximum and minimum power
must be performed in the indicated sequence and only by
qualified installer, service agency or gas supplier.
Before making the adjustments:
− remove the locking screw
− pull the front panel outwards and then to the top to re-
move it from points A.
A
A
CO2 ADJUSTMENT AT MAXIMUM POWER
− Press the MENU button, select "System test" and press ●
button to confirm.
Menu
"
"
Domestic Hot Water (DHW)
"
Information
"
"
Settings
"
"
System Test
"
"
− select "Max. power" with the ▲ / ▼ buttons and press ●
button to confirm. The fan starts turning at its maximum
speed (which can vary based on the model).
System Test
"
"
Test State
"
"
Fan Speed
"
"
Ionization
"
"
− the appliance will operate at maximum power.
− remove the cap (1) and insert the combustion analyzer
probe
− set the CO2 with a screwdriver on the adjustment screw (2)
on the gas valve, thus reaching the value reported on the
table.
Gas type
Natural Gas
LPG (Propane)
85
COMMISSIONING AND MAINTENANCE
"
High Power
"
"
0
rpm
"
"
0.0 A
CO2% maximum power
8.8-9.2
10.2-10.6