5.19 FEEDER BOTTLE FUNCTION
The Feeder Bottle function is used to block the value of the
DHW setpoint, to prevent anyone from accidentally modifying
it. To activate the function from the setpoint DHW screen:
1
press
2
and
press > 2 sec
3
to deactivate "Loc" press again

5.20 SCREED HEATER FUNCTION

With the system at a low temperature, the "screed heater"
function enables a heating request with a delivery setpoint of
20°C in the initial zone. This value is then gradually increased
as shown in the table below.
DAY
TIME
1
0
6
12
18
2
0
12
3
0
4
0
5
0
6
0
7
0
This function lasts 168 hours (7 days).
To activate the screed heater function:
ƒ set the boiler to OFF (because this function is only availa-
ble in this mode)
ƒ set 409 = 1, the display will show
---
Once activated, this function takes maximum priority. If there is
a power failure and reset, the function will resume from the point
where it was interrupted.
The screed heater function can be disabled by bringing the
boiler to a condition other than OFF, or by setting 409 = 0.
In item I001 of the INFO menu, you can see the number of
hours that have elapsed since the function was activated.
26
5 7 2
.
5 7 2
.
L c o
TEMPERATURE
20°C
22°C
24°C
26°C
28°C
30°C
32°C
35°C
35°C
30°C
25°C
R c S

5.21 COMBUSTION ANALYSIS

b
Checks to verify the adjustments of the CO2 values in
relation to the reference parameters (given in the tables
below) must be carried out with the casing closed. If the
casing is opened, the values will have to be reduced by
about 0.2% depending on the installation configuration
(the type and length of the discharge and suction pipes).
Combustion control sequence
1
---
The probe for the fumes analysis must
be inserted until it reaches the stop
---
Co
+
> 2 sec
The displayed value refers to the number of revolutions divi-
ded by 100.
ƒ Set the maximum rpm value
7
0 0
.
The boiler works at the maximum power level.
ƒ Check the analyser to ensure the max CO
with the indication given in the table. If the value is different,
calibrate the gas valve - see paragraph "5.23 Gas valve
calibration".
METHANE GAS
CO
max
2
(G20)
26C
9,0
30C
9,0
ƒ Set the minimum rpm value
6
0 1
.
The boiler works at the minimum power level.
ƒ Check the analyser to ensure the min CO
with the indication given in the table. If the value is different,
calibrate the gas valve - see paragraph "5.23 Gas valve
calibration".
METHANE GAS
CO
min
2
(G20)
26C
9,0
30C
9,0
3
2
4
0 0 6
.
fan speed
0 0 6
.
or
MAX
rpm
7
0 0
.
confirm
value complies
2
LPG
(G31)
10,0
10,0
6
0 1
.
MIN
rpm
confirm
value complies
2
LPG
(G31)
10,0
10,0
in CH
MAX
MIN
%
%
%
%