Master Conn 1 to 4 Read only. Shows the IP addresses of any other masters connected to this instrument.

6.2.5 BACnet

This allows the user to configure the instrument so as to allow it to be used as a BACnet device on a BACnet/
IP BMS network.
Device ID
Port
Password
BBMD Status
BBMD IP Address
BBMD Port
BBMD TTL
Rx Count
Tx Count
Reset Counts
6.3

GROUP CONFIGURATION

Group configuration is separated into two areas, one which defines trending characteristics (for display
channels) the other defining the recording characteristics for saving data to the Flash memory ready for
archiving.
Page 68
FEC920: USER GUIDE
Device ID
Password
BBMD Status
BBMD IP Address
BBMD Port
BBMD TTL
Rx Count
Tx Count
Reset Counts
Figure 63 BACnet configuration menu
The instance ID for this instrument. Must be unique on the network. Range is 0 - 4194302.
The BACnet I/P standard port is 47808. Valid values are: 1024 - 65535.
The BACnet password for Remote Device Management. Default is '100'. Maximum 20
characters.
Enable or disable registration of the instrument as a foreign device. Default is 'x'
(disabled).
The IP address of this instrument as a BACnet/IP Broadcast Management Device. Default
is 0.0.0.0.
The port this instrument communicates through as a BACnet/IP Broadcast Management
Device. Standard Port is 47808. Range is 1024 - 65535.
The Time to Live for this instrument as a BACnet/IP Broadcast Management Device. The
default value is '60'. Range is 0 - 65535.
A count of messages received.
A count of messages transmitted.
Set to 'Yes' and the Rx and Tx Counts are reset to zero. Once the counts are reset, this
option reverts to 'No'.
A5E45696052A Rev-AA
Network.BACnet
0
Port
47808
**********
X
0.0.0.0
47808
60
0
0
No