6.15.2 Sample and Hold details

As described above, Output follows Input1 as long as Input 2 is 'High'. When Input 2 goes Low, the output
adopts the instantaneous value of Input 1 until Input 2 goes High again. When Input 2 goes high the output
jumps to the current value of Input 1 and tracks it until Input 2 goes low.
6.16

TIMER

This 'Toolkit' option allows the user to configure up to four timers as: 'On Pulse', 'On Delay', 'One Shot' or 'Min
On' types. The different types are described in Section 6.16.2, below.

6.16.1 Parameters

Mode
Time
Elapsed time
Trigger in
Output
Triggered
Page 110
FEC920: USER GUIDE
Input 1
Input 2
Output
Output
Output
tracks
Input 1
Figure 98 Sample and Hold example
Elapsed Time
Trigger In
Triggered
Figure 99 Timer configuration
Select 'On pulse', 'On delay', 'One shot' or 'Min On'
Allows the user to enter a period for the timer.
This read-only parameter shows timing progress
Shows if the trigger source is active (tick) or inactive (cross)
Shows if the output is on (tick) or off (cross)
Shows if the timer is currently triggered (can remain triggered even after the trigger source
has returned to off).
A5E45696052A Rev-AA
Output
Output
held
tracks
held
Input 1
Timer.1
Mode
Off
Time
00:00:00
00:00:00
Output
Output
tracks
Input 1