Figure 8.9 Span Calibration - Advantech Adam 4000 Series User Manual

Data acquisition modules
Hide thumbs Also See for Adam 4000 Series:
Table of Contents

Advertisement

4.
Execute the Span Calibration command. This can be done through the ADAM
utility software. (Please see "A/O 10 V Calibration" option in the Calibration sub-
menu of the ADAM utility software.)
5.
Check the actual output value at the terminals. If this does not equal 0 V or 10 V,
use the Trim Calibration command to change the output value. This is done
through the ADAM utility software. (Use the arrow key to adjust the output value
after executing the "A/O 0V Calibration" or "A/O 10 V Calibration". Right and Up
keys mean increasing, and Left and Down keys mean decreasing).

Figure 8.9 Span Calibration

277
ADAM-4000 Series User Manual