Advantech Adam 4000 Series User Manual page 272

Data acquisition modules
Hide thumbs Also See for Adam 4000 Series:
Table of Contents

Advertisement

4080D
7.2.4.12
@AAPA(data)
Name
Description Set the low-alarm count value for counter 0 of the specified
Syntax
Response
Example
ADAM-4000 Series User Manual
Set Low-alarm Count Value for Counter 0 command
counter module.
@AAPA(data)(cr)
@ is a delimiter character.
AA (range 00-FF) represents the 2-character hexadecimal
address of the module.
PA is the Set Low-alarm Count Value for Counter 0 command.
(data) is the low-alarm count value which must consist of
eight hexadecimal digits. This value should be lower than
the high alarm value.
(cr) is the terminating character, carriage return (0Dh).
!AA(cr) if the command is valid.
There is no response if the module detects a syntax or
communication error, or even if the specified address does not exist.
! is a delimiter character which indicates a valid command
AA (range 00-FF) represents the 2-character hexadecimal
address of the module.
(cr) is the terminating character, carriage return (0Dh).
command: @12PA0000FFFF(cr)
response: !12(cr)
The command sets the low-alarm count number
0000FFFF(hex) for channel 0 of the counter modules at
address 12. The addressed module replies that the
command has been received.