Table 7.3: Baud Rate Codes - Advantech Adam 4000 Series User Manual

Data acquisition modules
Hide thumbs Also See for Adam 4000 Series:
Table of Contents

Advertisement

? is a delimiter character which indicates an invalid command.
AA (range 00-FF) represents the 2-character hexadecimal
address of the module.
(cr) is the terminating character, carriage return (0Dh).
Example
command: %0120510600(cr)
response: !20(cr)
The ADAM 4080D module is configured by changing
address 01 to a new address 20, choosing frequency
measurement module, assigning 9600 to baud rate, setting
frequency gate time 0.1 second and no checksum checking
or generation.
The response indicates that the command was received.
Wait seven seconds to let the new configuration settings
take effect before you issue a new command to the module.

Table 7.3: Baud Rate Codes

Baud Rate Code (Hex)
03
04
05
06
07
08
Caution! You can change all configuration parameters dynamically except check-
sum and baud rate parameters. They can only be altered when the INIT*
terminal is grounded.
Baud Rate
1200 bps
2400 bps
4800 bps
9600 bps
19.2 kbps
38.4 kbps
217
ADAM-4000 Series User Manual