Advantech Adam 4000 Series User Manual page 204

Data acquisition modules
Hide thumbs Also See for Adam 4000 Series:
Table of Contents

Advertisement

Table 6.3: ADAM-4024 Command Review:
#AAECn(data)
#**
$AA0Cn
$AA1Cn
$AA2
$AA3Cn(m)
$AA4
$AA5
$AA6Cn
$AA7CnRxx
ADAM-4000 Series User Manual
Set data As CHn Emergency Stop Data
Synchronous Sample IDI
Set Current Trim Data As CHn 4m A
Calibration Parameter/EEPROM
Set Current Trim Data As CHn 20m A
Calibration Parameter/EPROM
Read Back Module Status
Set Trim Data For CHn
m :0 ~ 127
And If Negative Then Add 0x80 (m =xx )
Ex.m=89
-9 m=09
+9
Read Back The IDI Input By Synchronous
Command (#**)
Checks the Reset Status of the analog
output module to see whether it has been
reset since the last Reset Status
command was issued.
Read Back CHn Last Output Value
Set CHn Output Type
AA:
Current Module Address
Cn: Channel
C: Prefix Command String
n = 0,1,2,3
Rxx: Output Type (Range)
R: Prefix Command String
xx = 32
-10 V ~ +10 V
xx = 30
0 ~ 20 mA
xx = 31
4 ~ 20 mA
190
!AAECn (data)
#02EC2 +07.456
#02EC1 -03.454
#02EC0 +11.234
No Response
#**
!AA
$020C2
!AA
$021C2
!AATTCCFF
$022
!AA
$02308
!AAx
$024
!AAS
$025
!AA(data)
$026C2
!AA
$027C2R32

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents