4080D
7.2.4.11
@AACA
Name
Description Both alarm states (High and Low) of the addressed counter
Syntax
Response
Example
Clear Latch Alarm command
module are set to OFF, no alarm.
@AACA(cr)
@ is a delimiter character.
AA (range 00-FF) represents the 2-character hexadecimal
address of the module.
CA is the Clear Latch Alarm command.
(cr) represents terminating character, carriage return (0Dh).
!AA(cr) if the command was valid.
There is no response if the module detects a syntax or
communication error, or even if the specified address does not exist.
! is a delimiter character which indicates a valid command.
AA represents the 2-character hexadecimal address of the module.
(cr) represents terminating character, carriage return (0Dh).
command: @05CA(cr)
response: !05(cr)
The counter module at address 05h is instructed to set
both alarm states (High and Low) to OFF. The module
confirms that it has done so.
257