Table 4.21: Adam-4055 Command Table - Advantech Adam 4000 Series User Manual

Data acquisition modules
Hide thumbs Also See for Adam 4000 Series:
Table of Contents

Advertisement

Table 4.21: ADAM-4055 Command Table

Command Syntax Command Name
%AANNTTCCFF
Configuration
#AABB(data)
Digital Data Out
Synchronized
#**
Sampling
$AA2
Configuration Status
Read Synchronized
$AA4
Data
$AA5
Reset Status
$AA6
Digital Data In
Read Firmware
$AAF
Version
$AAM
Read Module Name
$AAX0TTTTDD
Write Safety Value
$AAX1
Read Safety Value
$AAX2
Read Safety Flag
Command Description
Sets the address, baud rate, and/or
checksum status to a digital I/O
module
Writes specified values to either a
single channel or all channels simul-
taneously
Orders all digital I/O modules to
sample their input values and store
them in special registers
Returns the configuration parameters
of a specified digital I/O module
Returns the value of a specified digi-
tal I/O module that was stored in the
specified register after an #** com-
mand was issued
Indicates whether a specified digital
I/O module was reset after the last
time that $AA5 command was issued
Returns the values of the digital I/O
channel in the addressed module
Return the firmware version code
from the specified digital I/O module
Return the module name from the
specified digital I/O module
Force the DO channels to safety sta-
tus when communication is time-out
and over pre-defined period.
Read the time-out setting and pre-
defined safety status of DO channels.
Requests the Safty Flag of the
addressed digital I/O module to see
whether the safety value has been
executed since Write Safety Value
command was set.
107
ADAM-4000 Series User Manual
Page No.
7-4
7-8
7-11
7-14
7-12
7-16
7-6
7-18
7-19
7-21
7-22
7-23

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents