Source For Each Input Type; Table 4.9: Adam-4017+ Input Range And External Calibrating Input Source For Each Input Type - Advantech Adam 4000 Series User Manual

Data acquisition modules
Hide thumbs Also See for Adam 4000 Series:
Table of Contents

Advertisement

Table 4.8: ADAM-4017+ Command Table
$AA6
$AA0Ci
$AA1Ci
$AA7CiRrr
$AA8Ci
$AAXnnnn
$AAY
Table 4.9: ADAM-4017+ Input range and external calibrating input

source for each input type

Range
bcode(Hex)
07
08
09
0a
0b
0c
0d
ADAM-4000 Series User Manual
Read Channel Status
Single Channel
Span Calibration
Single Channel
Offset Calibration
Single Channel
Range Configuration
Read Single Chan-
nel Range Configura-
tion
Watchdog Timer
Setting
Read Watchdog
Timer Setting
Input Range
Max. Signal
4~20 mA
+20.000
+/-10 V
+10.000
+/-5 V
+5.0000
+/-1 V
+1.0000
+/-500 mV
+500.00
+/-150 mV
+150.00
+/-20 mA
+20.000
Get the enable/disable status of all
channels in an analog module
Calibrates a specified channel to cor-
rect for gain errors
Calibrates a specified channel to cor-
rect for offset errors
Configure the input type and range of
the specified channel in an analog
input module
Get the input type and range of the
specified channel in an analog input
module
Set communication WDT cycle time
from 0000 ~ 9999 (unit: 0.1 second. if
value is 0000, the communication
WDT function will be disable)
Read the cycle time setting of com-
munication WDT
Min Signal
+4.000 1
-10.000
-5.0000
-1.0000
-500.00
-150.00
-20.000
96
5-18
5-27
5-28
5-29
5-30
5-31
5-32
Displayed
Resolution
uA
1mV
100.00uV
100.00uV
10uV
10uV
1uA

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents