American Standard Selectronic 606B.X10 Installation Instructions Manual page 12

Proximity concealed urinal flush valve

Advertisement

SET DETECTION RANGE
C
(if required); Fig. 15 & 16
Note: The detection distance is preset and ideal for most
installations. Should an adjustment be required, follow the
steps below.
1. Remove COVER PLATE (1). See Step A for removing front
panel instructions.
2. Disconnect SENSOR CABLE (2) from BATTERY HOLDER
(3) or from POWER SUPPLY 27" EXTENSION CABLE (4).
Fig. 15.
3. Keeping hands away from the sensor detection area,
reconnect the SENSOR CABLE (3) and quickly hang the
COVER PLATE (1) onto the wall box. Do not secure the
COVER PLATE (1) at this time. Fig. 15.
Note: You have 5 seconds to begin entering the program
code after power connection is made.
4. While the SENSOR CONTROL LED (5) is blinking slowly,
place your hand 1 to 2". (30-50mm.) in front of the sensor.
Fig. 16.
5. When the LED (5) stops blinking and stays "ON" , move your
hand to the desired position from sensor and hold in place
until the LED (5) begins to blink again. Fig. 16.
Note: Detection Zone is 400mm - 800mm.
(Factory Setting: 400mm)
6. Once the SENSOR CONTROL LED (5) begins to blink
again, remove your hand from the detection zone. When
the flashing stops, the detection distance is set.
7. Replace and secure COVER PLATE (1). Fig. 16.
8. Actuate the FLUSH VALVE:
A) Cover sensor with hand for 10 seconds.
Note: Stand outside of sensor detection area.
B) Remove hand from in front of the sensor; unit will flush
in approximately 3 seconds.
Fig. 16
5
BLINKING
LED
1" - 2" (30mm - 50mm)
1
1
12
Fig. 15
2
3
4
5
DETECTION ZONE
BLINKING
400mm - 800mm
LED
(Factory Setting: 400mm)
1
M965643 Rev. 1.6 (11/16)