OUTPUT SERVICE MODE:
"Standard mode"
All pre-alarms, UV or IR detections are disabled. Information is sent in case of
confirmed alarm only.
"Expertise mode"
Current outputs, relays and LEDs, will be activated on pre-alarm, UV or IR detection
(Ref 6.3).
6.8.3.2.
This menu allows label and zone's modification. After selecting a label or a zone, the
modification function operates in the same manner.
Both "Label" and "Zone" fields are free text type for identification of the detector (name and
position of the detector).
To edit fields, Select [label] or [zone]:
Press on the corresponding numeric key to select a figure.
Press [>>] to go to the next figure in the field.
Press [PAGE] to go next page.
6.8.3.3.
[Set] / [Config] / [Outputs]
This menu gives access to the configuration of the relay operating mode and to conditions of
activations.
:
STATE OF THE RELAYS
Each relay can be configured:
Normally open (not energized)
Normally closed (energized)
ACTIVATION OF THE RELAYS:
Each relay can be activated on one or several following conditions:
-
IR detection (Service mode only)
-
UV detection (Service mode only)
-
Pre-alarm (Service mode only)
-
Alarm
-
UV detection fault
-
IR detection fault
-
On all fault
-
Inhibition
MAINTENANCE INHIBITION:
Sets how the temporary maintenance inhibition (power up, optical test, etc.) affects the
outputs. Choose "Frozen" (factory setting) or "Free". More details in §6.2.
MultiFlame DF-TV7
Label and zone sub-menu
Output
Page 38 / 56
NOSP16358-03 [04/2016]

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MultiFlame DF-TV7-T and is the answer not in the manual?

Subscribe to Our Youtube Channel

This manual is also suitable for:

Multiflame df-tv7-v

Table of Contents

Save PDF