4.2.3.
Sunshade / bad weather protection
A sunshade / weather protection (AS056-450) in light and resistant material (UV resistant) is
available. Mounted above the detector, it gives an additional protection against sun and bad
weather.
4.2.4.
Detector cartridge visor
The detector is fitted with a short visor for protection of the optical
detector window (standard). There are two additional models available if
further protection is required.
AS040: Long visor with no horizontal coverage reduction
AS041: Long visor with side blinker.
4.2.5.
Cable's inputs (as an option)
Connection cables must pass through a cable gland (Explosion Proof certified)
For installation details, refer to the instructions provided by the manufacturer of the cable
gland used.
The unassigned cable glands entries must be blanked with explosion proof
certified plugs (M20).They are glued with Loctite (tubétanche 577) or equivalent
compound. If a plug is moved or removed, it must be glued again with Loctite or an
equivalent.