Toshiba Ups Shutdown Events Setup - Toshiba RemotEye 4 User Manual

4 ups network card
Hide thumbs Also See for RemotEye 4:
Table of Contents

Advertisement

11.1.3

Toshiba UPS Shutdown Events Setup

RemotEye 4 can help further protect critical load systems connected to a UPS by initiating automated shutdowns on
that equipment. RemotEye 4 can shutdown servers/clients upon detection of UPS events: Input Power Failure,
Battery Low, UPS Overload, UPS System Overheat, EMD Temperature Over Threshold, EMD Alarm-1, EMD
Alarm-2, Recurring On/Off Schedule, and Non-Recurring On/Off Schedule. Also, RemotEye 4 can be used to
coordinate automatic system shutdowns during weekends or holidays. This section highlights the manners in which
RemotEye 4 can be used in conjunction with a UPS to manage power to UPS loads.
11.1.3.1 UPS Shutdown Events
RemotEye 4 can initiate output shutdown upon the occurrence of nine different UPS events Input Power Failure,
Low Battery, UPS Overload, UPS System Overheat, EMD Temperature Over Threshold, EMD Alarm-1, EMD
Alarm-2, Recurring On/Off Schedule and Non-recurring On/Off Schedule. Users can view the current setting of
these events in the UPS Shutdown Events widget on the RemotEye 4 Dashboard, or web page UPS
MANAGEMENT → UPS Shutdown Events. See Table 5-2 Widget Parameter List by Product Line.
To alter these settings, log in as an administrator, and configure the UPS shutdown events action and delay times
accordingly. Click the Set Value button when finished.
Scenario:
Shutdown Event:
Action:
Shutdown Delay (sec):
Broadcast Notification (sec):
UPS Output Shutdown Delay (Sec):
UPS Events - AC failed
22 : 20 : 00
INVERTER
OUTPUT
SHUTDOWN
Client's local shutdown delay (Sec):
22 : 20 : 00
CLIENT ON
CLIENT OFF
98
Input Power Failure
Client Shutdown
420 (default)
30 (default)
180 (default)
22:20:00
22 : 27 : 00
22 : 30 : 00
120(default)
22 : 27 : 00
22 : 29 : 00
RemotEye 4 User Manual – 90988-007