Bacnet Binary Input Point Mapping For 4300 - Toshiba RemotEye 4 User Manual

4 ups network card
Hide thumbs Also See for RemotEye 4:
Table of Contents

Advertisement

C.2

BACNET BINARY INPUT POINT MAPPING FOR 4300

ALL – BACnet Object: Binary Input
Access:
Read Only
Inst. ID
1
RemotEye 4 Data Link
2
RemotEye 4 Network Link
3
Online Mode
4
Backup Mode
5
Bypass Mode
6
Shutdown Mode
7
UPS Battery Status Unknown
8
UPS Battery Status Normal
9
UPS Battery Status Low
10
UPS Battery Status Depleted
11
UPS Battery Status Discharging
12
UPS Battery Status Test Failure
13
Protective Charging Set
14
Equalized Charging Set
15
Battery Test Disabled
16
Battery Test in Progress
17
EMD Enabled
18
EMD Alarm-1
19
EMD Alarm-2
174
BACnet Property: Present Value
Status Flags:
Normal
4300 BACnet Binary Input Point Mapping
Object Name & Description
Out of Service: FALSE
Units
True/False (1/0)
0 = Link Up; 1 = Link Down
True/False (1/0)
0 = Link Up; 1 = Link Down
True/False (1/0)
True/False (1/0)
True/False (1/0)
True/False (1/0)
True/False (1/0)
True/False (1/0)
True/False (1/0)
True/False (1/0)
True/False (1/0)
True/False (1/0)
True/False (1/0)
True/False (1/0)
True/False (1/0)
True/False (1/0)
True/False (1/0)
0 = no Alarm; 1 = Alarm Triggered
True/False (1/0)
(upsAlarmEMDSensor1AlarmTriggered)
0 = no Alarm; 1 = Alarm Triggered
True/False (1/0)
(upsAlarmEMDSensor2AlarmTriggered)
Comments
RemotEye 4 User Manual – 90988-007