Inst. ID
Object Name & Description
27
Output Number of Phases
28
Output Voltage
29
Output Rated Voltage
30
Output Current
31
Output Load Percentage
32
Output Rated Current
33
Output Frequency
34
Output Rated Frequency
35
Output Active Power
36
Output Rated Active Power
37
Output Apparent Power
38
Output Rated Apparent Power
39
Output Rated Power Factor
40
Bypass Number of Phases
41
Bypass Voltage
42
Bypass Current
43
Bypass Frequency
44
Bypass Apparent Power
45
DC Bus Total Voltage
46
Battery Installation Date
47
Estimated Battery Runtime
48
Number of Discharges
49
Elapsed Time on Battery Power
50
Estimated Battery Life Remaining
51
Battery Voltage
52
Battery Capacity
53
Battery Discharge Current
54
Rated Low Battery Voltage
55
Rated Battery Shutdown Voltage
56
Rated Battery Ampere Hour
57
Batteries in Series
58
Batteries in Parallel (Strings)
59
Temperature in Celsius
60
Temperature Fahrenheit
61
Humidity
RemotEye 4 User Manual – 90988-007
T1000 BACnet Analog Point Mapping
Units
Phase
Volts
Volts
0.1 Amps
%
0.1 Amps
0.1 Hz
0.1 Hz
Watts
kWatts
VA
VA
0.1 Unitless
Phase
Volts
0.1 Amps
0.1 Hz
VA
Vdc
Date
Minutes
Times
Seconds
Months
Vdc
%
0.1 Adc
Vdc
Vdc
Ahr
Batteries
Strings
°C
°F
%
Comments
Month Format: MM/DD/YYYY
Note: "-1" means disabled or not connected
Note: "-1" means disabled or not connected
Note: "-1" means disabled or not connected