MODBUS (3X) INPUT REGISTERS – 4300, 4400, AND 5000 SERIES PLATFORMS
Registers
Data Type
30818
Unsigned Integer
30819
Unsigned Integer
30820
Unsigned Integer
30821
Unsigned Integer
...
N/A
....
N/A
.....
N/A
30850
N/A
30851
Signed Integer
30852
Signed Integer
...
N/A
....
N/A
.....
N/A
30900
N/A
Note: The Modbus registers table style addressing is protocol base 0. If monitoring software uses PLC style addressing base 1, add one to the register number. For
Note 2: Please make sure the latest RemotEye 4 firmware revision is installed in order to use the Modbus register table below. If not, there will be inconsistencies
between RemotEye 4 internal register addressing and this manual. Go to www.toshibaups.com to get the latest RemotEye 4 firmware.
Note 3: There are some parameters that take two Modbus registers to display the correct data, since one register can only go up to 65536 (2^16). Use the following
formula (with example) to calculate the correct value: (Register 1* 0x10000) + Register 2 = Correct Unit Value
e.g. (Register (30276) * 0x10000) + Register (30277) = Correct Value in Watts