I.2

BACNET BINARY INPUT POINT MAPPING FOR 5000 (3P1)

ALL – BACnet Object: Binary Input
Access:
Read Only
Instance ID
Object Name & Description
1
RemotEye 4 Data Link
2
RemotEye 4 Network Link
3
Online Mode
4
Backup Mode
5
Bypass Mode
6
Start Inverter
7
Stop Inverter
8
Bypass Inverter On
10
UPS Battery Status Unknown
11
UPS Battery Status Normal
12
UPS Battery Status Low
13
UPS Battery Status Depleted
14
UPS Battery Status Discharging
16
Protective Charging Set
17
Equalized Charging Set
18
Battery Charger Status Normal Charging
19
Battery Charger Status Stop Charging
20
Battery Charger Status Discharging
23
EMD Enabled
24
EMD Alarm-1
25
EMD Alarm-2
26
General Alarm Fault
Open Fuse Fault
27
EPO has Tripped
RemotEye 4 User Manual – 90988-007
BACnet Property: Present Value
Status Flags:
Normal
5000 (3P1) BACnet Binary Point Mapping
Out of Service: FALSE
Units
Comments
True/False (1/0)
0 = Link Up; 1 = Link Down
True/False (1/0)
0 = Link Up; 1 = Link Down
True/False (1/0)
True/False (1/0)
True/False (1/0)
True/False (1/0)
True/False (1/0)
True/False (1/0)
True/False (1/0)
True/False (1/0)
True/False (1/0)
True/False (1/0)
True/False (1/0)
True/False (1/0)
True/False (1/0)
True/False (1/0)
True/False (1/0)
True/False (1/0)
True/False (1/0)
0 = no Alarm; 1 = Alarm Triggered
True/False (1/0)
(upsAlarmEMDSensor1AlarmTriggered)
0 = no Alarm; 1 = Alarm Triggered
True/False (1/0)
(upsAlarmEMDSensor2AlarmTriggered)
True/False (1/0)
1 = One or more fault reported, see below for cause; 0 = No Faults
True/False (1/0)
True/False (1/0)
213