Appendix G- Bacnet Point Mapping For T1000; Bacnet Analog Input Point Mapping For T1000 - Toshiba RemotEye 4 User Manual

4 ups network card
Hide thumbs Also See for RemotEye 4:
Table of Contents

Advertisement

APPENDIX G– BACNET POINT MAPPING FOR T1000
G.1

BACNET ANALOG INPUT POINT MAPPING FOR T1000

ALL – BACnet Object: Analog Input
Access:
Read Only
Inst. ID
Object Name & Description
1
RemotEye 4 Software Version
2
RemotEye 4 Slave ID Number
3
IP Address
4
Subnet Mask
5
Gateway IP Address
6
RemotEye 4 Installation Date
7
Date on RemotEye 4
8
Time on RemotEye 4
9
UPS Manufacturer
10
UPS Typeform
11
UPS Serial Number
12
UPS Capacity
13
UPS Installation Date
14
UPS Firmware Version
15
UPS Battery Temperature
16
UPS Battery Temperature
17
Input Numbers of Phases
18
Input Voltage
19
Input Voltage Percent
20
Input Current
21
Input Current Percent
22
Input Rated Current
23
Input Frequency
24
Input Total Active Power
25
Input Rated Active Power
26
Input Apparent Power
200
BACnet Property: Present Value
Status Flags:
Normal
T1000 BACnet Analog Point Mapping
Out of Service: FALSE
Units
Comments
Firmware
Example: 1.00
ID
IP Address
Example: 192.168.1.150
Subnet Mask
Example: 255.255.255.0
IP Address
Example: 192.168.1.1
Date
MM/DD/YYYY
Date
MM/DD/YYYY
Times
HH:MM:SS
Characters
Toshiba
Characters
UH3G2L036C61TPA3
Characters
2012101234567890
VA
Date
MM/DD/YYYY
Characters
°C
°F
RemotEye Converts °C to °F = °C * (9/5) + 32
Phase
Volts
%
0.1 Amps
%
0.1 Amps
0.1 Hz
Watts
Watts
VA
RemotEye 4 User Manual – 90988-007

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents