About Drive Programming
11.
AN-14 Terminal 53 Low Ref./Feedb. Value. Set
minimum speed reference on Terminal 53 at
20Hz. (This tells the drive that the minimum
voltage received on Terminal 53 (0V) equals 20Hz
output.)
5
5
12.
AN-15 Terminal 53 High Ref./Feedb. Value. Set
maximum speed reference on Terminal 53 at
50Hz. (This tells the drive that the maximum
voltage received on Terminal 53 (10V) equals
50Hz output.)
With an external device providing a 0-10V control signal
connected to drive terminal 53, the system is now ready
for operation. Note that the scroll bar on the right in the
last illustration of the display is at the bottom, indicating
the procedure is complete.
Illustration 5.1 shows the wiring connections used to
enable this set up.
30
AF-600 FP Operating Instructions
Illustration 5.1 Wiring Example for External Device Providing
0-10V Control Signal
5.3 Control Terminal Programming
Examples
Control terminals can be programmed.
See Table 2.2 for control terminal parameter number and
default setting. (Default setting can change based on the
selection in K-03 Regional Settings.)
The following example shows accessing Terminal 18 to see
the default setting.
1.
Each terminal has specified functions it is capable
of performing
Parameters associated with the terminal enable
the function
For proper drive functioning, the control
terminals must be
Wired properly
Programmed for the intended function
Receiving a signal
Press [Main Menu] twice, scroll to Parameter Data
Set and press [OK].