Uploading Data To The Keypad; Downloading Data From The Keypad; Restoring Default Settings; Recommended Initialisation - GE AF-600 FP Operating Instructions Manual

Fan & pump drive
Hide thumbs Also See for AF-600 FP:
Table of Contents

Advertisement

User Interface

4.2.1 Uploading Data to the keypad

1.
Press [OFF] to stop the motor before uploading
or downloading data.
2.
Go to K-50 Keypad Copy.
3.
Press [OK].
4.
Select All to keypad.
5.
Press [OK]. A progress bar shows the uploading
process.
6.
Press [Hand] or [Auto] to return to normal
operation.

4.2.2 Downloading Data from the keypad

1.
Press [OFF] to stop the motor before uploading
or downloading data.
2.
Go to K-50 Keypad Copy.
3.
Press [OK].
4.
Select All from keypad.
5.
Press [OK]. A progress bar shows the
downloading process.
6.
Press [Hand] or [Auto] to return to normal
operation.

4.3 Restoring Default Settings

CAUTION
Initialisation restores the unit to factory default settings.
Any programming, motor data, localization, and
monitoring records will be lost. Uploading data to the
keypad provides a backup prior to initialisation.
Restoring the drive parameter settings back to default
values is done by initialisation of the frequency converter.
Initialisation can be through H-03 Restore Factory Settings
or manually.
Initialisation using H-03 Restore Factory Settings
does not change drive data such as operating
hours, serial communication selections, personal
menu settings, fault log, alarm log, and other
monitoring functions
Using H-03 Restore Factory Settings is generally
recommended
Manual initialisation erases all motor,
programming, localization, and monitoring data
and restores factory default settings
AF-600 FP Operating Instructions

4.3.1 Recommended Initialisation

1.
2.
3.
4.
5.
6.
7.
Default parameter settings are restored during start up.
This may take slightly longer than normal.
8.
9.

4.3.2 Manual Initialisation

1.
2.
Factory default parameter settings are restored during start
up. This may take slightly longer than normal.
Manual initialisation does not reset the following drive
information
Press [Main Menu] twice to access parameters.
Scroll to H-03 Restore Factory Settings.
Press [OK].
Scroll to Initialisation.
Press [OK].
Remove power to the unit and wait for the
display to turn off.
Apply power to the unit.
Alarm 80 is displayed.
Press [Reset] to return to operation mode.
Remove power to the unit and wait for the
display to turn off.
Press and hold [Status], [Main Menu], and [OK] at
the same time and apply power to the unit.
ID-00 Operating Hours
ID-03 Power Up's
ID-04 Over Temp's
ID-05 Over Volt's
4
4
27

Advertisement

Table of Contents
loading

Table of Contents