Warnings and Alarms
No.
Description
50
Auto Tune calibration failed
51
Auto Tune check U
and I
nom
52
Auto Tune low I
nom
53
Auto Tune motor too big
54
Auto Tune motor too small
55
Auto Tune Parameter out of range
56
Auto Tune interrupted by user
57
Auto Tune timeout
58
Auto Tune internal fault
59
Current limit
60
External Interlock
62
Output Frequency at Maximum Limit
64
Voltage Limit
65
Control Board Over-temperature
66
Heat sink Temperature Low
67
Option Configuration has Changed
69
Pwr. Card Temp
70
Illegal Drive configuration
76
Power Unit Setup
79
Illegal PS config
80
Drive Initialized to Default Value
91
Analog input 54 wrong settings
92
NoFlow
93
Dry Pump
94
End of Curve
95
Broken Belt
96
Start Delayed
97
Stop Delayed
98
Clock Fault
201
Fire M was Active
202
Fire M Limits Exceeded
203
Missing Motor
204
Locked Rotor
243
Brake IGBT
244
Heatsink temp
245
Heatsink sensor
246
Pwr.card supply
247
Pwr.card temp
248
Illegal PS config
250
New spare parts
251
New Type Code
Table 8.1 Alarm/Warning code list
(X) Dependent on parameter
1)
Cannot be Auto reset via H-04 Auto-Reset (Times)

8.4.1 Fault Messages

The warning/alarm information below defines the warning/
alarm condition, provides the probable cause for the
condition, and details a remedy or troubleshooting
procedure.
WARNING 1, 10 Volts low
The control card voltage is below 10 V from terminal 50.
AF-600 FP Operating Instructions
Warning
nom
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Alarm/Trip
Alarm/Trip Lock
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Remove some of the load from terminal 50, as the 10 V
supply is overloaded. Max. 15 mA or minimum 590 Ω.
This condition can be caused by a short in a connected
potentiometer or improper wiring of the potentiometer.
Troubleshooting: Remove the wiring from terminal 50. If
the warning clears, the problem is with the customer
wiring. If the warning does not clear, replace the control
card.