Application Set-Up Examples
Table 6.8 External Alarm Reset
Table 6.9 Speed Reference (using a manual potentiometer)
AF-600 FP Operating Instructions
Parameters
Function
Setting
E-02 Terminal 19
[1] Reset
Digital Input
* = Default Value
Notes/comments:
Parameters
Function
Setting
AN-10 Terminal
53 Low Voltage
0.07V*
AN-11 Terminal
10V*
53 High Voltage
AN-14 Terminal
0*
53 Low Ref./
Feedb. Value
AN-15 Terminal
50*.
53 High Ref./
Feedb. Value
* = Default Value
Notes/comments:
Table 6.10 Run Permissive
Hand Off Auto (HOA), without the use of the Drive keypad
To have a HOA system with an external 0-10V potenti-
ometer for the hand reference and a 4-20mA signal for the
auto reference, 2 set-ups should be used. In this example
set-up 1 is used for the hand mode and set-up 2 for the
auto mode. Analog input 53 is used for the hand reference
(0-10V potentiometer) and analog input 54 for the auto
reference (4-20mA) and digital input 27 for the set-up
selector. Please ensure that the analog inputs have the
correct dip settings (A-53 [U] and A-54 [I]).
In the upper right corner of the keypad 2 numbers are
shown – like 1(1). The number outside the parenthesis is
the active set-up and the number inside the parenthesis is
the set-up which will be edited. Default will always be 1(1).
Make sure you edit set-up 1.
1.
Make all the parameter changes you need, that
will be common for auto and hand mode, like
motor parameters etc.
2.
Set par. K-10 Active set-up to [9] Multi Set-up.
This parameter change is needed to be able to
change set-up from an external source, like a
digital input.
3.
Set par. K-11 Edit Set-up to [9] Active Set-up. This
is recommended because then the active setup
Parameters
Function
Setting
E-01 Terminal 18
Digital Input
[8] Start*
E-02 Terminal 19
[52] Run
Digital Input
Permissive
E-03 Terminal 27
[7] External
Digital Input
Interlock
E-24 Function
[167] Start
Relay
command
act.
* = Default Value
Notes/comments:
43
6
6