GE AF-600 FP Operating Instructions Manual page 72

Fan & pump drive
Hide thumbs Also See for AF-600 FP:
Table of Contents

Advertisement

Specifications
Surroundings:
Unit Size 1x types
Unit Size 21 and 22 types
Unit Size 23 and 24 types
Unit Size 31 and 32 types
Unit Size 33 and 34 types
Unit Size 41, 42, and 51 types
Unit Size 43, 44, and 52 types
Unit Size 61/63
Unit Size 62/64
IP21/Nema 1 kit for all unit sizes 1x, 2x, and 3x
Vibration test all enclosure types
Relative humidity
Aggressive environment (IEC 60068-2-43) H
Test method according to IEC 60068-2-43 H2S (10 days)
Ambient temperature (at 60 AVM switching mode)
- with derating
- with full output power of typical EFF2 motors (up to 90% output current)
- at full continuous Drive output current
1)
For more information on derating see the AF-600 FP Design Guide, section on Special Conditions.
Minimum ambient temperature during full-scale operation
Minimum ambient temperature at reduced performance
Temperature during storage/transport
Maximum altitude above sea level without derating
Maximum altitude above sea level with derating
Derating for high altitude, see section on special conditions
EMC standards, Emission
EMC standards, Immunity
See section on special conditions!
Control card performance:
Scan interval
Control card, USB Serial Communication:
USB standard
USB plug
CAUTION
Connection to PC is carried out via a standard host/device USB cable.
The USB connection is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
The USB connection is not galvanically isolated from protection earth. Use only isolated laptop/PC as connection to the USB
connector on drive or an isolated USB cable/converter.
AF-600 FP Operating Instructions
5% - 95% (IEC 721-3-3; Class 3K3 (non-condensing) during operation
S test
2
EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6
IP 20/Chassis, IP 21kit/Type 1, IP55/Type12
IP21/Type 1, IP54/Type12
IP21/NEMA 1/on top of enclosure
EN 61800-3, EN 61000-6-3/4, EN 55011, IEC 61800-3
EN 61800-3, EN 61000-6-1/2,
USB type B "device" plug
IP55/Type12
IP20/Chassis
IP55/Type 12
IP20/Chassis
IP00/Chassis
IP21, 54/Type1, 12
IP21, 54/Type1, 12
1.0g
class Kd
1)
max. 50°C
max. 50 °C
1)
max. 45 °C
1)
0°C
- 10°C
-25 - +65/70°°C
1000m
3000m
10
5 ms
1.1 (Full speed)
69
10