Specifications

10.3.2 CE Compliance

Fuses or Circuit Breakers are mandatory to comply with IEC 60364. GE recommend using a selection of the following.
The fuses below are suitable for use on a circuit capable of delivering 100,000 Arms (symmetrical), 240V, or 480V, or 500V,
or 600V depending on the drive voltage rating. With the proper fusing the drive short circuit current rating (SCCR) is
100,000 Arms.
AF-600 3-phase
[HP]
1
2
3
5
7,5
10
15
20
25
30
40
50
60
Table 10.7 200-240V, IP20/Open Chassis
AF-600 3-phase
[HP]
1
2
0
10
3
5
7,5
10
15
20
25
30
40
50
60
Table 10.8 200-240V, IP55/Nema 12
72
AF-600 FP Operating Instructions
Recommended fuse size
Recommended max fuse
gG-16
gG-20
gG-50
gG-80
gG-125
aR-160
aR-200
aR-250
Recommended fuse size
Recommended max fuse
gG-20
gG-63
gG-80
gG-125
aR-160
aR-200
aR-250
Recommended circuit breaker
gG-25
PKZM0-25
gG-32
gG-63
PKZM4-50
gG-125
NZMB1-A100
gG-150
NZMB2-A200
aR-160
aR-200
NZMB2-A250
aR-250
Recommended circuit breaker
gG-32
PKZM0-25
gG-80
PKZM4-63
gG-100
NZMB1-A100
gG-160
NZMB2-A200
aR-160
aR-200
NZMB2-A250
aR-250
Max trip level
[A]
25
50
100
150
250
Max trip level
[A]
25
63
100
160
250