Application Set-Up Examples
will always be the set-up that is edited. If you
prefer you can also ignore this and manually
control what set-up you want to edit through
par. K-11.
4.
Set par. E-03 Terminal 27 Digital Input to [23] Set-
up select bit 0. When terminal 27 is OFF, set-up 1
(hand) is active, when it is ON, set-up 2 (auto) is
active.
5.
Set par. F-01 Frequency Setting 1 to Analog input
53 (hand mode).
6.
Copy set-up 1 to set-up 2. Set par. K-51 Set up
Copy to [2] Copy to set-up 2. Now setup 1 and 2
are identical.
7.
If you need to be able to change between hand
and auto mode while the motor is running you
will have to link the 2 set-ups together. Set par.
K-12 This Set-up Linked to to [2] set-up 2.
6
6
8.
Change to set-up 2 by setting input 27 ON (if par.
K-11 is [9]) or by setting par. K-11 Edit Set-up to
set-up 2.
9.
Set par. F-01 Frequency Setting 1 to Analog input
54 (auto mode). If you want different settings in
hand and auto mode, like different accel/decel
ramps, speed limits etc. you can now programme
them. You just have to make sure you edit the
correct set-up. Set-up 1 is Hand mode and set-up
2 is Auto mode.
Table 6.11 HOA
44
AF-600 FP Operating Instructions
Parameters
Function
Setting
E-01 Terminal 18
Digital Input
[8] Start*
E-03 Terminal 27
[23[ Set-up
Digital Input
select bit 0
* = Default Value
Notes/comments:
GE 30mm HOA Cat# (1)
104PSG34B & (3) CR104PXC1
Table 6.12 RS-485 Network Connection (N2, FLN, Modbus RTU, Drive)
CAUTION
Thermistors must use reinforced or double insulation to
meet PELV insulation requirements.
Parameters
Function
Setting
O-30 Protocol
Drive*
O-31 Address
1*
O-32 Drive Port
9600*
Baud Rate
* = Default Value
Notes/comments:
Select protocol, address and
baud rate in the above
mentioned parameters.