Commissioning

5.7 System Start-up

The procedure in this section requires user-wiring and
application programming to be completed. The following
procedure is recommended after application set-up is
completed.
1.
Press [Auto On].
2.
Apply an external run command.
3.
Adjust the speed reference throughout the speed
range.
4.
Remove the external run command.
5.
Check sound and vibration level of the motor to
ensure that the system is working as intended.
If warnings or alarms occur, see or chapter 7.4 List of
Warnings and Alarms.
MG16E322
Instruction Manual