Danfoss FC 103 Instruction Manual page 18

Vlt refrigeration drive 1.1–90 kw
Hide thumbs Also See for FC 103:
Table of Contents

Advertisement

Electrical Installation
4
4
1
9
1
PLC
2
Adjustable frequency drive
3
Output contactor
4
Grounding rail (PE)
5
Cable insulation (stripped)
Figure 4.2 EMC-compliant Electrical Connection
NOTICE!
EMC INTERFERENCE
Run cables for input power, motor wiring and control wiring in three separate metallic conduits. Failure to isolate
power, motor and control cables can result in unintended behavior or reduced performance. Minimum 7.9 in [200 mm]
clearance between power, motor and control cables is required.
16
2
10
L1
L2
L3
PE
8
Danfoss A/S © Rev. 2014-04-10 All rights reserved.
Instruction Manual
11
6
Cable connector
7
Motor, 3-phase and PE
8
Line power, 3-phase and reinforced PE
9
Control wiring
10
Equalizing min. 0.025 in
6
3
4
5
U
V
W
PE
7
2
2
[16 mm
]
MG16E322

Advertisement

Table of Contents
loading

Table of Contents