Danfoss FC 103 Instruction Manual page 63

Vlt refrigeration drive 1.1–90 kw
Hide thumbs Also See for FC 103:
Table of Contents

Advertisement

Specifications
8.8.1 CE Compliance
200–240 V
Enclosure
Power (hp [kW])
type
A2
1.5–3 [1.1–2.2]
A3
4–5 [3.0–3.7]
B3
7.5–15 [5.5–11]
B4
20–24 [15–18]
C3
30–40 [22–30]
C4
50–60 [37–45]
A4
1.5–3 [1.1–2.2]
A5
0.34–5 [0.25-3.7]
B1
7.5–15 [5.5–11]
B2
15
C1
24–40 [18–30]
C2
50–60 [37–45]
Table 8.8 200–240 V, Enclosure Types A, B and C
MG16E322
Instruction Manual
Recommended
fuse size
gG-10 (1.5–2 [1.1–1.5])
gG-16 (3 [2.2])
gG-16 (4 [3])
gG-20 (5 [3.7])
gG-25 (7.5–10 [5.5–7.5])
gG-32 (15 [11])
gG-50 (20 [15])
gG-63 (25 [18])
gG-80 (30 [22])
aR-125 (40 [30])
aR-160 (50 [37])
aR-200 (60 [45])
gG-10 (1.5–2 [1.1–1.5])
gG-16 (3 [2.2])
gG-10 (0.34–2 [0.25–1.5])
gG-16 (3–4 [2.2–3])
gG-20 (5 [3.7])
gG-25 (7.5 [5.5])
gG-32 (10–15 [7.5–11])
gG-50
gG-63 (25 [18.5])
gG-160 (25–30 [18.5–22])
gG-80 (30 [22])
gG-100 (40 [30])
aR-160 (50 [37])
aR-200 (60 [45])
Danfoss A/S © Rev. 2014-04-10 All rights reserved.
Recommended
Recommended circuit
max. fuse size
breaker (Moeller)
gG-25
PKZM0-25
gG-32
PKZM0-25
gG-63
PKZM4-50
gG-125
NZMB1-A100
gG-150 (22)
NZMB2-A200
aR-160 (30)
aR-200 (50 [37])
NZMB2-A250
aR-250 (60 [45])
gG-32
PKZM0-25
gG-32
PKZM0-25
gG-80
PKZM4-63
gG-100
NZMB1-A100
NZMB2-A200
aR-160 (40 [30])
aR-200 (50 [37])
NZMB2-A250
aR-250 (60 [45])
Max. trip level [A]
25
25
50
3.94 [100]
150
250
25
8
25
63
100
160
250
61
8

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the FC 103 and is the answer not in the manual?

Questions and answers

Table of Contents