Operating Instructions Fire alarm system EBL512, V2.7.x

Commissioning an installation

Before you connect the power supply to a control unit, all other cable
connections shall be made. Check once more that they are correct.

Single Control Unit

1. Take away the rectifier fuse (F1) and a battery fuse (F2 or F3) on
the charger board 1557 / 1657.
2. Connect the batteries to the charger board 1557 / 1657.
3. Connect the rectifier to the mains (230 V AC).
4. Replace the rectifier fuse (F1) and the battery fuse (F2 or F3) on
the charger board 1557 / 1657.
5. LED "Operation" (L6) indicate that the 24 V DC power supply
(rectifier and/or battery) is okay.
6. An automatic restart will now take place (see chapter "Restart",
page 88.
7. The site specific data (SSD) can now be downloaded, see chapter
"Programming (SSD download)", page 81. (The SSD is created
via the PC program Win512.)
8. See also chapter "Calibration of supervised outputs (H5/A1)",
page 127.

Control Units in a TLON network

In a TLON network there is two or more control units connected. A
TLON connection board 1590 is required in each control unit
connected to the network.
70
cables are connected
, for each control unit, do as follows:
1. Take away the rectifier fuse (F1) and a battery fuse (F2 or F3) on
the charger board 1557 / 1657.
2. Connect the batteries to the charger board 1557 / 1657.
3. Connect the rectifier to the mains (230 V AC).
4. Replace the rectifier fuse (F1) and the battery fuse (F2 or F3) on
the charger board 1557 / 1657.
5. LED "Operation" (L6) indicate that the 24 V DC power supply
(rectifier and/or battery) is okay.
69
In a mixed system (see chapter "Mixed system", page 12) the EBL512
c.i.e. has to have the software version 2.7.x.
70
The TLON connection board is mounted on the main board 1556.
Network cable connections are made on the connection board 1555 (T.B. P1).
77
69
When the 1590 board is on place and the