Panasonic EBL512 Operating Instructions Manual page 20

Fire alarm system ebl512
Hide thumbs Also See for EBL512:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01457
Rev: -
Push button
P1
Alarms queued (black)
P2
Silence buzzer (yellow)
P3
Silence Alarm devices (red)
11
P4
Reset (green)
P5
Evacuate (green)
Operating Instructions Fire alarm system EBL512, V2.7.x
Push buttons on the Fire Brigade Panel (FBP)
Operation/function
Used, when LEDs "Alarms queued" (L2) are lit, to
scroll/browse through the queued alarms (zones). Function,
see chapter "Fire alarm", page 41, under LEDs "Alarms
queued".
Used to silence the buzzer in the c.i.e.
10
Used to silence the sounders (i.e. outputs for alarm devices).
Has to be pressed for > 0.5 sec.
Used to reset the fire alarm(s).
Used to reset co-incidence alarm.
14
Used to activate the sounders (i.e. outputs for alarm devices).
10
In the New Zealand convention = the "inside switch".
11
In Belgian, British Standard and British Standard Marine Application
conventions has "P3" to be activated before "P4" can be used.
12
Multiple reset (Default): All fire alarms in the system will be reset
simultaneously. Single reset: The fire alarm displayed in the LCD (first row
to the left) will be reset. When more than one fire alarm is generated (LEDs
"Alarms queued" are lit) each fire alarm has to be individually reset. Single
encapsulated reset: Fire alarm reset is like "Single reset". Encapsulation
function is described in EBL512 Planning Instructions, chapter "System
properties (settings). (Encapsulated unit / zone = disabled unit / zone.)
NOTE (1)! When "Multiple reset" or "Single reset" is used, encapsulated
reset can be done by pressing "Reset" (P4) and 0.1 sec. later also press
"Alarms queued" (P1) and hold them pressed for > 0.5 sec.
By Single reset: The fire alarm displayed in the LCD (first row to the left)
will be encapsulated.
By Multiple reset: The fire alarm displayed in the LCD (first row to the left)
will be encapsulated or the points in alarm status within one zone will be
encapsulated or the whole zone (conventional) will be encapsulated.
NOTE (2)! When "Single reset" or "Single encapsulated reset" is used you
can make a "Multiple reset" by pressing "Reset" (P4) and 0.1 sec. later also
press "A" (in the keypad) and hold them pressed for > 0.5 sec.
13
Co-incidence alarm = One unit / zone in a 2-unit (-zone) dependence is
activated.
14
In some conventions this button is not used (no designation text).
In Belgian, British Standard, Hungarian and Ukrainian conventions this
button is used for the "Evacuate" function.
In "Polish" (CNBOP), "Bulgarian" and "Czech" conventions this button is
used for "Alert Annunciation Acknowledge".
In "Australian" and "New Zealand" conventions this button is used to disable
all zones "in alarm".
18
12
13