Disable or re-enable (H2)

A whole zone, one or more alarm points within a zone and/or control
outputs can be disabled via menus H2/B1-B3. This possibility can be
used when a temporary disablement is wanted (e.g. craftsmen working
in the premises, etc.).
The function Enhanced disablement is enabled as default i.e.
disabled alarm points will not activate Pre-warning, fire alarm or fault.
If this function is not enabled (via Win512), fault can be activated but
not pre-warning or fire alarm. (This is a violation to the EN54-2
standard.
Addressable manual call points can be disabled (but shall normally not
be disabled).
However, when a whole zone is disabled, the
addressable manual call points will not be disabled for safety reasons.
Up to 512 whole zones can be disabled via menu H2/B1.
Up to 200 alarm points (zones / address) can be individually
disabled via menu H2/B2 and/or COM / BS4 loops, zone interface
inputs and/or MIO inputs can be disabled via menu H8/S2. (Alarm
points disabled via time channels are not limited and must not be
counted!)
Up to 200 outputs can be individually disabled via menu H2/B3.
Disabled output will stay in (or return to) the normal condition for the
output respectively. (Disabled outputs via menu H2/B8 and menu
H2/B9 are not limited and must not be counted!)
Up to 200 Interlocking outputs can be individually disabled via
menu H9/C4. (All interlocking outputs disabled via "000/00" are not
limited and must not be counted!)
It is not possible to exceed the limits. A warning will be shown:
Max. disablements reached!
Disablement not performed.
Don't forget to re-enable (via menus H2/B4-B6, B8 or B9, H8/S3,
H9/C5 or use automatic re-enablement for zones and alarm points.
Disablements are indicated by LED "Disablements" (L8) and are also
94
shown in the display
. An example:
Zone 001 is disabled
More... is indicating two or more disablements.
Disablements (and faults) are indicated by a 2-sec. beep when an open
control unit door is being closed.
94
NOTE! See chapter "Alphanumeric display (LCD) in EBL512", page 22
regarding priority order.