Panasonic Eco Solutions Nordic AB
MEW01457
Rev: -
Operating Instructions Fire alarm system EBL512, V2.7.x
or
The key cabinet has not been closed within 5 minutes after reset of all
fire alarms in the system.
FAULT: L-C mixed COM-loop x, CU xx
The two wires L (SA) and C (SB) have been mixed (alternated). Check
so that the wire connections are correct according to drawing 512-41.
FAULT: LON-board 1590, control unit xx
(TLON connection board, 1590)
No communication / connection with the TLON network. The board
has to be changed.
FAULT: Loop unit technical number xxxxxx
The communication with the unit is not all right, i.e. the unit is out of
order / faulty.
FAULT: Low battery capacity, CU xx
Battery internal resistance is too high. The check is performed every
th
12
hour.
The battery might be too old.
Cables, fuses etc. for externally placed batteries might cause a
voltage drop.
Check / adjust the rectifier (power supply) voltage (24 V DC).
Check the charging voltage over the battery respectively (13.5-
13.8 depending on the actual charging step).
Check the voltage over a disconnected battery (fully charged >
13 V).
In the New Zealand convention only:
The battery charging is turned off 60 minutes every 24
battery voltage < 24.4 V during these 60 minutes will generate a fault.
If a fault is generated it will automatically be Serviced after these 60
minutes.
FAULT: Low main PWS, control unit xx
Mains voltage below 187 V AC. Blown fuse (230 V AC) or no
67
th
hour. A