16.2.3
16.2.4
16.2.5
Operating Instructions Fire alarm system EBL512, V2.7.x
If more than one fire alarm is activated (i.e. LEDs "Alarms queued"
(L2) are lit) the next fire alarm in the queue is now shown in the
display, on the first row to the left. It has to be reset the same way as
the first one.
When all fire alarms are reset, LEDs "Fire" (L1) and "Alarms
queued" (L2) are turned OFF and the display is empty.
All outputs (for fire alarm) are now also reset, i.e. de-activated.
If a key cabinet is installed, the key (to the building) has to be put
back into the key cabinet within 5 minutes. If not, a fault will be
generated and a fault message will be shown in the display, see
chapter "Key cabinet alarm reset, page 53.

Single encapsulated reset

Like "Single reset" but with an encapsulation function as well:
Normally when an alarm point or zone (having activated fire alarm) is
reset when still in alarm status, it will activate a new fire alarm within
20 seconds. (According to the EN54-2 standard.)
When "Single encapsulated reset" is performed, an alarm point or
zone still in alarm status, will not only be reset but also disconnected,
i.e. it will not activate a new fire alarm within 20 seconds. It has to be
re-enabled via menu H2/B5 before it can activate a new fire alarm.
(This function, set in Win512, is a violation to the EN54-2 standard.)
LED "Disablements" (L8) is indicating one or more disablements in
the system.
NOTE!
When "Multi reset" or "Single reset" is used, encapsulated reset can be
done by pressing "Reset" (P4) and 0.1 sec. later also press "Alarms
queued" (P1) and hold them pressed for > 0.5 sec.
By Single reset and by Multiple reset: The fire alarm displayed in the
LCD (first row to the left) will be reset and disabled or the points in
alarm status within one zone will be reset and disabled or the whole
zone (conventional) will be reset and disabled.

Alert Annunciation

Regarding the function, see chapter "Alert Annunciation (AA alarm)",
page 46 and EBL512 Planning Instructions, chapter "Alert
annunciation". Reset of the AA alarm(s) can be done via push button
"Reset" on an AA unit 1735 / 1736 or an AA controller 1740 (or in the
c.i.e.). If more than one AA alarm is activated, they will be reset all at
a time.
NOTE! Reset via an external unit is only possible to do during the
investigation time and AA alarm(s) only (not normal fire alarms).

Co-incidence alarm

A Co-incidence alarm can be manually reset with the "Reset" button
(P4) on the c.i.e. front or automatically reset after 5 minutes (i.e. if the
52
60