Panasonic EBL512 Operating Instructions Manual page 121

Fire alarm system ebl512
Hide thumbs Also See for EBL512:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01457
"A"
"Return"
"Return"
"A"
Restart
See chapter "
", page 88.
Rev: -
Operating Instructions Fire alarm system EBL512, V2.7.x
Algorithm for sensor 000001 is changed
from N-15
to N-35
Enter technical number: 000000
Alarm algorithms have been changed. The
affected CU:s will now restart. ACCEPT?
Sensor values
Printout: (1=yes)
NOTE!
The new algorithm will not be in use until after the restart.
In case of an automatic log off (and one or more algorithms are
changed), the affected control unit(s) will restart.
Perf. Factor = Performance factor:
Low (min. 0) = The detector is mounted in a "stable" environment.
High (max. 2.55) = The detector is mounted in an "unstable" environment.
See also Planning Instructions, chapter "Performance factor".
119
Write the sensor's techn.
number and/or press "A"
to accept or press
"Return" to carry out the
change of algorithm(s).
Menu U5 will be shown
U5
for a few seconds and
then the affected control
unit(s) will restart.